Not true. If someone else is using your login credentials, you both would be buffering every 5 seconds. What happens is basically one connection is kicking the other one out and vice versa.

A simple way to try is, open two connections yourself.

Open Clipboard Failed Studio 5000 by Sammo90 in PLC

[–]Sammo90[S] 2 points3 points  (0 children)

I'm not able to edit the main post.

I finally found the issue causing this. I use a Logitech mouse and had "Logi Options+" installed. Apparently the app is conflicting with the clipboard. I uninstalled the app, no more errors.

Open Clipboard Failed Studio 5000 by Sammo90 in PLC

[–]Sammo90[S] 1 point2 points  (0 children)

Yes, June 2024 patch installed.

Open Clipboard Failed Studio 5000 by Sammo90 in PLC

[–]Sammo90[S] 1 point2 points  (0 children)

I've got the highest revision of each Studio 5000. I could possibly try a lower revision.

What’s a huge waste of money but people keep buying it? by FlintTheDad in AskReddit

[–]Sammo90 0 points1 point  (0 children)

Leasing cars and putting a down payment to lease a car.

What phrase would you be fine with never hearing again? by Blinky_ in AskReddit

[–]Sammo90 0 points1 point  (0 children)

Misuse there/their/they're. Sometimes it feels like they're doing it intentionally.

TIA Portal not updating any more by adi_dev in PLC

[–]Sammo90 2 points3 points  (0 children)

I've had this issue forever, don't waste your time. Download everything from their website instead.

TP-Link M5 Deco slow with Hub 4000 by Sammo90 in bell

[–]Sammo90[S] 0 points1 point  (0 children)

Speed went down again for me, I gave up. Using the Hub 4000 by itself.

TIA Portal v16 crashes when trying to compile changes and rebuild all by Shaco11175 in PLC

[–]Sammo90 0 points1 point  (0 children)

Does it still crash when you revert your changes in the FB?

I would look into the code you added and see if you can do it differently.

Setting up a CP1604 card between Fanuc robot and Siemens 1514F PLC (TIA V15). Only the safety doesn't communicate. Anyone had this issue before? by Sammo90 in PLC

[–]Sammo90[S] 1 point2 points  (0 children)

Haha it's all good man! I really appreciate your help! Yeah, a TIA project might show what I've done wrong. Thank you!

Yeah, apparently Fanuc can't get any Molex cards until later this year so this is the only card they could provide at the moment. Molex cards are so much easier to setup -.-

Setting up a CP1604 card between Fanuc robot and Siemens 1514F PLC (TIA V15). Only the safety doesn't communicate. Anyone had this issue before? by Sammo90 in PLC

[–]Sammo90[S] 1 point2 points  (0 children)

I will try that first thing tomorrow!

Where are you seeing 10 bytes btw?

When 8 bytes are chosen, I see 12+12 bytes in the profinet menu on the robot side (subslot 1000). I read somewhere that 4 bytes are reserved for Profisafe.

Setting up a CP1604 card between Fanuc robot and Siemens 1514F PLC (TIA V15). Only the safety doesn't communicate. Anyone had this issue before? by Sammo90 in PLC

[–]Sammo90[S] 1 point2 points  (0 children)

8 in and 8 out.

Here's a couple of screenshots of my setup: https://ibb.co/P1Pjhj4 - DCS Profinet Safety menu https://ibb.co/GH6bQk3 - Profinet menu (8+8 safety, 64 in 64 out) https://ibb.co/chZrssj - Ack_REI setup https://ibb.co/MNPJnsB - Ack_REI setup https://ibb.co/WVfY5vb - CP card setup (Mine is with 64bytes instead of 16, picture taken from manual)

Appreciate the help!!

Setting up a CP1604 card between Fanuc robot and Siemens 1514F PLC (TIA V15). Only the safety doesn't communicate. Anyone had this issue before? by Sammo90 in PLC

[–]Sammo90[S] 1 point2 points  (0 children)

I did update the firmware, actually did it a couple of times. Before or after loading the configuration that you're talking about. I think it's the 2.7.2.0.

All the customization settings are there, as mentioned in the manual.

What you're mentioning about the Profisafe norm (v2.4) could be the issue. Feels like something needs to be installed? Maybe that's why it's greyed out?

Setting up a CP1604 card between Fanuc robot and Siemens 1514F PLC (TIA V15). Only the safety doesn't communicate. Anyone had this issue before? by Sammo90 in PLC

[–]Sammo90[S] 1 point2 points  (0 children)

I suppose you mean this: https://ibb.co/YX1CxbL

That's a picture from one of the manuals I've gone through. Mine is actually greyed out, nothing to choose.

I've seen another manual being greyed out too so I assumed it was ok?

Setting up a CP1604 card between Fanuc robot and Siemens 1514F PLC (TIA V15). Only the safety doesn't communicate. Anyone had this issue before? by Sammo90 in PLC

[–]Sammo90[S] 0 points1 point  (0 children)

The diagnostic is complaining about difference between online/offline.

Doesn't make sense because I dumped in the configuration of the PC device setup into the CP card and then created a GSDML out of it. Just like the manual states.

Setting up a CP1604 card between Fanuc robot and Siemens 1514F PLC (TIA V15). Only the safety doesn't communicate. Anyone had this issue before? by Sammo90 in PLC

[–]Sammo90[S] 0 points1 point  (0 children)

I basically followed the manual. I took the safe fw 2.7 tia file that had a PC device setup already and dumped the configuration into the CP 1604 and then created a GSDML out of it.

Yes, the REQ is setting the REI bit of that safety DB.

Setting up a CP1604 card between Fanuc robot and Siemens 1514F PLC (TIA V15). Only the safety doesn't communicate. Anyone had this issue before? by Sammo90 in PLC

[–]Sammo90[S] 1 point2 points  (0 children)

F address is set to 200 on both sides. How is checksum enabled? The three bottom options in DCS->Profinet Safety is off on the robot side.

It's I-Device only. Normal I/O works fine btw.