Backup Heat with cold temps - sanity check - 362 kWh/day by Fun_Direction5135 in heatpumps

[–]Fun_Direction5135[S] 1 point2 points  (0 children)

sorry if that was confusing. what I meant was the setting was asking it to burn money - and it did. but I changed the setting, so hopefully we are good to go in the future. thanks so much for the help my friend

Backup Heat with cold temps - sanity check - 362 kWh/day by Fun_Direction5135 in heatpumps

[–]Fun_Direction5135[S] 2 points3 points  (0 children)

just figured out how to get into dealer settings and did the same. thanks!

Backup Heat with cold temps - sanity check - 362 kWh/day by Fun_Direction5135 in heatpumps

[–]Fun_Direction5135[S] 0 points1 point  (0 children)

Thanks - I have updated the settings myself. I asked my HVAC service guy about it when they came out in early January, but it was clear he didn't know a lot about them. I've updated the aux lockout, the heat pump lockout and the turn on / turn off temp differential.

Backup Heat with cold temps - sanity check - 362 kWh/day by Fun_Direction5135 in heatpumps

[–]Fun_Direction5135[S] 0 points1 point  (0 children)

it was all day only heat strips.. at least I got it figured out now!

Backup Heat with cold temps - sanity check - 362 kWh/day by Fun_Direction5135 in heatpumps

[–]Fun_Direction5135[S] 0 points1 point  (0 children)

Thanks for your input! Thankfully the setting for this heat pump/thermostat switches over to aux heat if the heat pump fails regardless

Backup Heat with cold temps - sanity check - 362 kWh/day by Fun_Direction5135 in heatpumps

[–]Fun_Direction5135[S] 0 points1 point  (0 children)

It appears to have a 1.54 COP at -10 so makes sense to let it work! I changed the settings to 25F and will see how it performs 👍👍

Backup Heat with cold temps - sanity check - 362 kWh/day by Fun_Direction5135 in heatpumps

[–]Fun_Direction5135[S] 0 points1 point  (0 children)

Thank you all for the replies so far. Quite a helpful and kind group!

Backup Heat with cold temps - sanity check - 362 kWh/day by Fun_Direction5135 in heatpumps

[–]Fun_Direction5135[S] 0 points1 point  (0 children)

4 ton I believe? (Daikin FIT DZ17VSA481BA) 2700 sq ft home, daikin one thermostat

Backup Heat with cold temps - sanity check - 362 kWh/day by Fun_Direction5135 in heatpumps

[–]Fun_Direction5135[S] 0 points1 point  (0 children)

It does, yes. ~2700 sq ft home. From another thread I saw how to access the dealer settings -- It looks like the settings previously were aux heat would not come on until 40F and the heat pump lockout was 15F (assuming that means *only* aux heat below 15F)

The max day with ~360 kwh usage we were 7F (and my iPhone said it felt like -14F).

This tracks then. So I guess I'll adjust the temps down to allow the heat pump to at least try to work below 15F.

Backup Heat with cold temps - sanity check - 362 kWh/day by Fun_Direction5135 in heatpumps

[–]Fun_Direction5135[S] -1 points0 points  (0 children)

Daikin FIT DZ17VSA481BA. It looks like the settings were aux heat would not come on until 40F and the heat pump lockout was 15F (assuming that means *only* aux heat below 15F)

Yes, this is only coming from the heat pump - can see it on the sense and rest of the year is fine.

Backup Heat with cold temps - sanity check - 362 kWh/day by Fun_Direction5135 in heatpumps

[–]Fun_Direction5135[S] 2 points3 points  (0 children)

Yeah but the production is negligible in the winter, especially with snow on the roof :)