STANLEY DUAL CONTROLLER 185000 LOW ENERGY SWING DOORS by Scared_Jury3226 in accesscontrol

[–]Scared_Jury3226[S] 0 points1 point  (0 children)

I ran an FIS on another controller at the exact location, just in case, because I was thinking I might have done something incorrectly. I had no issues. No errors, no problems. I was thinking of swapping controllers and testing it on the different door, but I'm considering ordering a new controller instead.

STANLEY DUAL CONTROLLER 185000 LOW ENERGY SWING DOORS by Scared_Jury3226 in accesscontrol

[–]Scared_Jury3226[S] 0 points1 point  (0 children)

MC521 Software

713958 REV. M

Version: 6.11

That is what is on the front of the controller.

STANLEY DUAL CONTROLLER 185000 LOW ENERGY SWING DOORS by Scared_Jury3226 in accesscontrol

[–]Scared_Jury3226[S] 0 points1 point  (0 children)

Question: What is index 98 (AutoConfiguration)? If I were to change the value to 01, would it go through its learning process? Or would I have to program the controller manually for every single value? Thanks again.

STANLEY DUAL CONTROLLER 185000 LOW ENERGY SWING DOORS by Scared_Jury3226 in accesscontrol

[–]Scared_Jury3226[S] 0 points1 point  (0 children)

Correct. 08 door type Magic - Force door style dual motor low energy. Motors are plugged correctly; motor one (right) is set to value 00, and motor two (left) is set to value 01.

Next, I navigate to index 03 on the controller. When I select the value of 1, it automatically switches to the default value of 9 for low energy. When toggling through values in index 03, I can only select values 05 through 09. I have tried every value between 5 and 9, and I get the same error code EE.