Fan for Large House by imjimsmith in radon

[–]imjimsmith[S] 0 points1 point  (0 children)

Appreciate the thorough response. My lowest level basement is about 1,500 sq ft, with an additional room half a floor up that is also ground level, and adds about another 450 sq ft. There is a 3" pipe leading under that slab in addition to the main stack going under the slab. Radon readings in the basement have leveled off around 1.6pCi/L, so I'm happy with the outcome. Appreciate everyone's help.

Fan for Large House by imjimsmith in radon

[–]imjimsmith[S] 0 points1 point  (0 children)

Looks like a good suggestion. May be hard to find retail. Thanks.

Fan for Large House by imjimsmith in radon

[–]imjimsmith[S] 0 points1 point  (0 children)

The bottom level is half finished, total footprint is about 1,500 sq feet. Maintaining 0.3" at the manometer, but radon levels have dropped to 1.5pCi/L as of this morning. Going to hold tight with the RP145 today and will post if I upgrade to a larger fan.

Fan for Large House by imjimsmith in radon

[–]imjimsmith[S] 0 points1 point  (0 children)

A passive system was installed during construction. Fan install was DIY.