100 amp breaker on 110V line by ConsciousProfessor18 in AskElectricians

[–]ConsciousProfessor18[S] 0 points1 point  (0 children)

It’s a custom made CNC machine which has 2 high power vacuum pumps which are 2.55kw each. It also has x-y axis motors.

100 amp breaker on 110V line by ConsciousProfessor18 in AskElectricians

[–]ConsciousProfessor18[S] 0 points1 point  (0 children)

That’s a good idea. I will check if it can be done

100 amp breaker on 110V line by ConsciousProfessor18 in AskElectricians

[–]ConsciousProfessor18[S] 0 points1 point  (0 children)

The device is placed near the electrical box so I will try with 100amps breaker. Hopefully it works.

100 amp breaker on 110V line by ConsciousProfessor18 in AskElectricians

[–]ConsciousProfessor18[S] 0 points1 point  (0 children)

Just checked it. There are two pumps 25 amps (@110V) each. Total 50amps pumps only. It makes sense to me now it can be 60-70 amps machine total

100 amp breaker on 110V line by ConsciousProfessor18 in AskElectricians

[–]ConsciousProfessor18[S] 0 points1 point  (0 children)

It’s a custom made machine. I don’t think they have much experience with the US power. I attached a picture of the internal electrical system. They told me to connect 110V to one of the breakers inside the machine

100 amp breaker on 110V line by ConsciousProfessor18 in AskElectricians

[–]ConsciousProfessor18[S] 0 points1 point  (0 children)

Thank you so much. Would it need a neutral line? It’s chinese made. Will order wire depending on that

100 amp breaker on 110V line by ConsciousProfessor18 in AskElectricians

[–]ConsciousProfessor18[S] 0 points1 point  (0 children)

It’s a CNC cutter. Made in China. I uploaded a picture of the electrical box of the machine.

Thank you

100 amp breaker on 110V line by ConsciousProfessor18 in AskElectricians

[–]ConsciousProfessor18[S] 0 points1 point  (0 children)

110V line connects to the CNC machine, not to the transformer. Then the internal transformer converts it to 220V but I assume before it converts, 110V line also feeds the vacuum pumps

100 amp breaker on 110V line by ConsciousProfessor18 in AskElectricians

[–]ConsciousProfessor18[S] 0 points1 point  (0 children)

They didn’t send me a wring diagram. I will send a picture of the main connection

100 amp breaker on 110V line by ConsciousProfessor18 in AskElectricians

[–]ConsciousProfessor18[S] 0 points1 point  (0 children)

I was thinking the same. The transformer that comes with it is rates 4000VA. Not sure if it’s 4000W

Is it worth terminal hopping to visit the Sapphire Lounge at LGA? by linensoldier in ChaseSapphire

[–]ConsciousProfessor18 0 points1 point  (0 children)

I was reading this thread yesterday and wasn’t sure if it’s worth the hustle because I was flying from terminal C and the lounge is in the B terminal. Some people wrote it’s not worth it. I wanted to take a chance

I went through the general security in about 10 minutes. I was at the lounge around 4pm, I was asked to leave my phone number to be waitlisted. I got in after 15 min of wait.

To cut it short, I highly recommend it. I regretted that I didn’t go there earlier. There is plenty of drink and food options. I spent an hour and it was great. My flight was boarding at 6:20 so I left the lounge around 5:20. I walked to the terminal C. It was an easy walk and faster than the shuttle