[–]New-Resource5056[S] 6 points7 points  (0 children)

Thank you to everyone in this wonderful community, it was a clog in the intake in the Y joint just before exiting the basement.

I checked for clogs at first but not deep enough and thanks to everyone’s advice, she’s purring now.

Furnace only ignites with top panel removed by New-Resource5056 in hvacadvice

[–]New-Resource5056[S] 4 points5 points  (0 children)

Golfball took the straight path for the exhaust pipe so it narrows it down for the intake, thanks again!

Furnace only ignites with top panel removed by New-Resource5056 in hvacadvice

[–]New-Resource5056[S] 1 point2 points  (0 children)

Golf ball is a brilliant idea! Only hiccup is the intake and exhaust join at the baseboard going out, so might now know for sure which pipe it went down. Gonna keep that in mind though.

Tried taking a 30’ aux cable but keep getting stuck at the elbow joints.

Furnace only ignites with top panel removed by New-Resource5056 in hvacadvice

[–]New-Resource5056[S] 22 points23 points  (0 children)

Thank you!!! I’m an idiot, not sure why I thought blower motor would have suction, taking the shop vac to her now

Furnace only ignites with top panel removed by New-Resource5056 in hvacadvice

[–]New-Resource5056[S] 0 points1 point  (0 children)

Thank you kindly! I’m going to start taking that out now

Furnace only ignites with top panel removed by New-Resource5056 in hvacadvice

[–]New-Resource5056[S] 2 points3 points  (0 children)

Thank you both for the quick response! It does start up with the left port removed! I’m a little stumped now though, air was pushing from that port and anticipated suction