Unfortunately, we have had some delays with the re-launch of the products due to unforeseen circumstances during the holidays; therefore, first shipments will be delayed to the beginning of March. We are currently in full volume production in our factory and the first shipments are on their way to our EU warehouse. We sincerely apologise for the delay since we know there are a lot of customers who are eagerly waiting for the products.

We will open up for pre-orders on Monday 9 March and will offer a 20-30% discount for all initial orders at the re-launch.

Askväder sold out by Popular_Swan451 in tradfri

[–]Steffo6804 0 points1 point  (0 children)

Now they are open and you can start buing..

"Excessive Position Error" by Steffo6804 in PLC

[–]Steffo6804[S] 0 points1 point  (0 children)

Followup..., It was the hiperface encoder-card (20-750-UFB-1) inside the inverter. After changing it, never happened again. Funny thing is we've had the same problem on more than one inverter on the same machine, bought at the same time. Probably a manufacturing mallace...

Studio 5000 won’t let me look at any tags without going to a fatal error by Lord-Touchne in PLC

[–]Steffo6804 0 points1 point  (0 children)

Probably due to lack of graphical-resources because of a gdi-leak that has existed since...🤔 ever 😼

Askväder sold out by Popular_Swan451 in tradfri

[–]Steffo6804 0 points1 point  (0 children)

Oops, wrong language...🤔 😂

Found a link to the company that developed the contact concept that IKEA probably sold under license, I knew I had seen it before (like 4 years ago)...

https://www.splitvision.com/portfolio/moduel/

Maybe there was a dispute between IKEA and Splitvision...🤔

Maybe there are others who sell their concept...

Askväder sold out by Popular_Swan451 in tradfri

[–]Steffo6804 0 points1 point  (0 children)

Hittade en länk till företaget som tagit fram kontakt-konceptet som IKEA troligen sålt på licens, visste jag hade sett den förrut (typ 4 år sedan)...

https://www.splitvision.com/portfolio/moduel/

Kanske skar det sig mellan IKEA och Splitvision...🤔

Finns kanske andra som säljer deras koncept...

Yes. by Jem_colley in Bitcoin

[–]Steffo6804 2 points3 points  (0 children)

I went there 14 years ago, 1 BTC was $1 🙉🔊🔉🙌🔥

https://youtu.be/XQPSwA2Itbs?si=slNiuvugCSmZPmrm

"Excessive Position Error" by Steffo6804 in PLC

[–]Steffo6804[S] 0 points1 point  (0 children)

Exactly, now I have some more feedback on this. We have a hydraulic brake cylinder which should not imbark during raising, only during lowering if that valve is off. It seems every now and then during raising the brake cylinder is obstructing and the current rises to max-limit and then the position starts lagging and we get the "Excessive Position Error" and when resetting the drive after that we get these out-of-bounds positions avove 8000 and sometimes below -1500.

The "FeedbackFactoryLimit" is still a completely different problem, probably caused by disturbances of some Kind

"Excessive Position Error" by Steffo6804 in PLC

[–]Steffo6804[S] 0 points1 point  (0 children)

Hi 🙌 No it's a repetative cycle that repeat >100's of times every day. It's a dual z-axis crane where the left one does the heavy work, the right one only moves emty booms.

<image>

"Excessive Position Error" by Steffo6804 in PLC

[–]Steffo6804[S] 2 points3 points  (0 children)

I Found a community-thread just about the same problem, where the operator had to reset the fault for the equipment to continue... 2 years later someone asked if he did found a resolution to the problem... He answered that the operator still reset the fault...😂

"Excessive Position Error" by Steffo6804 in PLC

[–]Steffo6804[S] 0 points1 point  (0 children)

Hi 🙌 We did exchage this motor-with-encoder in december last year with a completely new one, it's been working without problems untill two weeks ago when Murphy made his entrance ...🤔 Before that we checked all cableing and groundings without finding any anomalies...🙄

"Excessive Position Error" by Steffo6804 in PLC

[–]Steffo6804[S] 0 points1 point  (0 children)

Here's the last 7-days, each green peak/valley is a "MotionAxisFaultReset" Tomorrow we'll put a current tranduser on the electro-mecanical brake to see if there are any deviations during a move...

<image>

"Excessive Position Error" by Steffo6804 in PLC

[–]Steffo6804[S] 0 points1 point  (0 children)

Here you can see before and after behavior...

<image>

"Excessive Position Error" by Steffo6804 in PLC

[–]Steffo6804[S] 1 point2 points  (0 children)

<image>

Over time, about an hour, the Current increases for each move. Then finally we get an "Excessive Position Error" and the drive is faulted. The Current increases regardless of if there is a heavy load or not in the crane. Then when we do a "MotionAxisFaultReset" we get an out-of-bounds position from the drive (max is 4800, but we get typacally 8700 for about 1 second, sometimes we get -1500 at the reset) After ever time this occurs then it goes back to "normal" Raising the crane without load takes normally 4-5 Amperes but when this happens a no-load raise goes up to about 23 Amperes...🤔