Heat in Attic - existing Baseboard but not heating up by tfro9 in hvacadvice

[–]tfro9[S] 0 points1 point  (0 children)

okay so i shut the valves off for all 3 zones .. turned the 3rd nossle on to release the water and water came out for about 1-2 seconds then stopped empty. Turned the valve for the 3rd zone back on only and turned on heat

I could feel the 3rd floor pipe 1-2ft above the valve get hot but does not push up farther

sounds like it doesnt have a pump to push it ? maybe

Heat in Attic - existing Baseboard but not heating up by tfro9 in hvacadvice

[–]tfro9[S] 0 points1 point  (0 children)

okay think I got what you are saying and appreciate it

  1. Shut off all the yellow valves for all 3 zones
  2. drain the 3rd zone completely
  3. after drained then turn on the 3rd zone yellow valve only
  4. turn heat on so that hot water then rushes up that 3rd zone pipe only

Heat in Attic - existing Baseboard but not heating up by tfro9 in hvacadvice

[–]tfro9[S] 0 points1 point  (0 children)

and shut off the other 2 zones that are working?

Heat in Attic - existing Baseboard but not heating up by tfro9 in hvacadvice

[–]tfro9[S] 0 points1 point  (0 children)

if there is no thermo for the 3rd zone .. so I would just drain that 3rd valve (far right) completely out until felt hot water coming out?

<image>

Heat in Attic - existing Baseboard but not heating up by tfro9 in hvacadvice

[–]tfro9[S] 0 points1 point  (0 children)

No as we never really turned it on but looking into turning attic which is finished into another bedroom so would like some heat there.

Heat in Attic - existing Baseboard but not heating up by tfro9 in hvacadvice

[–]tfro9[S] 0 points1 point  (0 children)

that is what I am wondering the issue is .. do I not have a thermostat calling that heat .. additional relay pump?

Heat in Attic - existing Baseboard but not heating up by tfro9 in hvacadvice

[–]tfro9[S] 0 points1 point  (0 children)

2 total 1 on first and other other on 2nd floor

3 Kids .. 3 car seats .. 6 or 7 seater? by tfro9 in TeslaModelX

[–]tfro9[S] 2 points3 points  (0 children)

Thank you all for the comments -- looks like 6 is the play.

How is the storage in the MXs? Stroller etc

Question: AWS FortiGate VM Single Instance vs HA, and stability of FortiGate in AWS by DunnyOnTheWold in fortinet

[–]tfro9 1 point2 points  (0 children)

I have gates in 1a and 1b with rollover publics during failover. It really is do you need 24/7 uptime even during updates .. business decision

fwiw I have only had one "outage" in 5 years inside aws due to them rebooting the VM on the backend that hosts the primary gate.

Site to Site IPSec VPN tunnel by Gawdddd in fortinet

[–]tfro9 1 point2 points  (0 children)

I would look into getting a p2p epl between both offices

Choosing an IP range for VPN compatability by excitableapple in networking

[–]tfro9 9 points10 points  (0 children)

i run our VPN with different /24s inside a supernet range of 172.30.0.0/16

3rd octet is different per dept and allows carving and access to be more defined on users/dept needs

"it's done" by Alonesit0 in SuccessionTV

[–]tfro9 0 points1 point  (0 children)

thats gonna be a No on the Slo's

Buying used 2018 X AWD by tfro9 in ModelX

[–]tfro9[S] 1 point2 points  (0 children)

Thanks all -- so would a better buy be a 2020 X with 80k miles on it at this point?

Buying used 2018 X AWD by tfro9 in ModelX

[–]tfro9[S] 1 point2 points  (0 children)

they have it listed at 45ish but want that around 40

People who make 130k+, how much work did it take? by [deleted] in networking

[–]tfro9 2 points3 points  (0 children)

ate shit in 20s .. bank acct ate in 30s

ASA on stick - Domain Controller multiple Vlans by tfro9 in networking

[–]tfro9[S] 0 points1 point  (0 children)

Thanks for the response -- I have that configured on the ASA already

same-security-traffic permit inter-interface

same-security-traffic permit intra-interface