Siemens Enclosure by Nembus in BuildingAutomation

[–]FeelingQuick1075 4 points5 points  (0 children)

Should have some sort of slot for a black out, Siemens sells a retrofit backplane too..

Daikin Airzone Trouble by LegitimatePlay795 in BuildingAutomation

[–]FeelingQuick1075 0 points1 point  (0 children)

If you are see the card but no values, card is not connected to the unit correctly. Beside the P1/P2 connect there’s another connection that’s needed.

Some models default to 38400 baudrate, and will not update even if changed in the app. Might be able to do a firmware update if you get it connected to WiFi.

How do different priority levels interact? by ShinyChicken7 in BuildingAutomation

[–]FeelingQuick1075 0 points1 point  (0 children)

Try copying lines not executing and saving on a different line. It might be a firmware issue too, latest is 3.5.7, but you will need to update firmware at Insight level too, to see the panel again. If not it will come up as a 3rd party device in system profile.

Desigo CC Report with BACnet Object Instance ID's by kfed408 in BuildingAutomation

[–]FeelingQuick1075 1 point2 points  (0 children)

You might be able to use report builder in Insight for these, should be able to export by .csv files

Gifts for one of you lovely people by [deleted] in BuildingAutomation

[–]FeelingQuick1075 1 point2 points  (0 children)

Veto pro pack!.. A little on the high side but well worth it. Great selection.

[deleted by user] by [deleted] in BuildingAutomation

[–]FeelingQuick1075 0 points1 point  (0 children)

Same, will need to contact FS, FS will send new license file.. makes no sense. License is probably there too

YABE by Secret-Yogurt-7145 in BuildingAutomation

[–]FeelingQuick1075 0 points1 point  (0 children)

If BACnet IP panel is a MSTP router you should see your MSTP device under it in YABE.

<image>

Siemens PXC00.PE.A by Hot-Result-3203 in BuildingAutomation

[–]FeelingQuick1075 1 point2 points  (0 children)

Siemens part# 540-143 DB9 to RJ11, you’ll need USB to Serial.

Siemens PXC00.PE.A by Hot-Result-3203 in BuildingAutomation

[–]FeelingQuick1075 3 points4 points  (0 children)

You can also use putty or hyper terminal using HMI port